Viessmann Boiler: Wall mounting bracket on concrete, wood and metal studs
Wall mounting bracket on concrete, wood and metal studs on a Viessmann boiler: The boiler mounts on a wall bracket. The supplied screws and rawl plugs are only for concrete. Other materials need bolts and anchors rated for 196 lb (86 kg). A loose bracket is a severe safety hazard, so it must be tight and level.
Applies to: Vitodens 100-W B1HE and B1KE wall-mounted
Common causes of wall mounting bracket on concrete, wood and metal studs
- Bracket not fully secured
- Wall material not suitable for the supplied fixings
How to fix wall mounting bracket on concrete, wood and metal studs: step by step
- Check the wall condition and confirm it can carry 196 lb (86 kg).
- Concrete: mark the holes, drill 10 mm holes, insert the rawl plugs, and fasten the bracket with the supplied screws.
- Wood studs: drill 3/16 in. pilot holes at the center of each stud and fasten with bolts.
- Metal studs: drill pilot holes at the center of each stud, use the supplied fasteners, and make sure the bracket is level.
- Check the bracket is tight and secure before hanging the boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W B1HE/B1KE installation manual, p. 13-14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.