Viessmann Boiler: Verify burner input by clocking the gas meter
Verify burner input by clocking the gas meter on a Viessmann boiler: Check actual gas input by timing the meter with all other gas appliances on the same meter switched off. Do not overfire the boiler. Running 5% under-fired is acceptable.
Applies to: Vitodens 100-W, WB1B, natural gas
How to fix verify burner input by clocking the gas meter: step by step
- Turn off all other gas equipment served by the meter.
- Time how many seconds the boiler takes to use 10 cu. ft. of gas.
- Calculate input as (3600 x 10) divided by the seconds, then multiply by the gas heating value in Btu per cu. ft.
- Example: 305 seconds and 1000 Btu/cu. ft. gives about 118,000 Btu/h for a 118,000 Btu/h boiler.
- Get the correct heating value from the gas utility before clocking the meter.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.