Viessmann Boiler: Testing the flow switches / flow sensors
Testing the flow switches / flow sensors on a Viessmann boiler: Both flow sensing devices shut the burner down on low flow and block restart until flow is restored. The test is done by throttling the water flow to or from the boiler; the boiler should shut down once flow drops below its safe set point.
Applies to: Models 112, 150, 399, 530
How to fix testing the flow switches / flow sensors: step by step
- Throttle the water flow to or from the boiler.
- Confirm the boiler shuts down when flow drops below the safe operating set point.
- Restore full flow and confirm the burner can restart.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.