Viessmann Boiler: Test the flow switch
Test the flow switch on a Viessmann boiler: The B2HA series has a flow sensing device. Low flow opens the switch, the burner shuts down and it will not restart until adequate flow returns.
Applies to: Vitodens 200-W B2HA 19, 28, 35
Common causes of test the flow switch
- Flow below the safe operating set point of the boiler
How to fix test the flow switch: step by step
- Throttle the water flow to or from the boiler.
- Confirm the boiler shuts down once flow drops below its safe operating set point.
- Restore full flow and confirm the burner restarts only after adequate flow is back.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.