Viessmann Boiler: System layout with three zone circuits and low-loss header
System layout with three zone circuits and low-loss header on a Viessmann boiler: Layout for DHW production plus three zone circuits. Total flow of the circuits can exceed the boiler's maximum flow, so a low-loss header is strongly recommended.
Applies to: Vitodens 200-W, B2HA/B 80 to 100, 285 to 352
How to fix system layout with three zone circuits and low-loss header: step by step
- Fit a low-loss header; it is available as an accessory.
- Use the AM1 extension module for zone circuits 2 and 3.
- Use a zone thermostat with dry contact for each zone circuit.
- Where the underfloor circuit needs low temperature, use a 3-way mixing valve with the mixing valve accessory kit.
- For underfloor tubing without an oxygen diffusion barrier, install system separation.
- Use corrosion-resistant materials on the secondary side of the heat exchanger.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.