Viessmann Boiler: System layout 8: DHW plus three zone circuits with low-loss header
System layout 8: DHW plus three zone circuits with low-loss header on a Viessmann boiler: Multiple Vitodens 200-W boilers with a low-loss header feeding three zone circuits through a thermostat-controlled zone arrangement, using the AM1 extension module for zones 2 and 3. Zone 1 uses boiler output 157.
Applies to: Multi-boiler with three zone circuits plus DHW
How to fix system layout 8: dhw plus three zone circuits with low-loss header: step by step
- Use a low-loss header; it is strongly recommended.
- Connect the DHW pump to output 21 and the boiler pump to output 20.
- Wire the zone 1 circuit to output 157.
- Install the AM1 extension module and wire zone circuits 2 and 3 to its outputs A1 and A2.
- Connect the zone thermostats as dry contacts.
- Connect the outdoor sensor, DHW sensor and supply temperature sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HB installation instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.