Viessmann Boiler: System Layout 6: B1KE with closely spaced tees
System Layout 6: B1KE with closely spaced tees on a Viessmann boiler: B1KE boiler with closely spaced tees and one heating circuit. A low-loss header is strongly preferred.
Applies to: B1KE 120, 199 with closely spaced tees
How to fix system layout 6: b1ke with closely spaced tees: step by step
- Space the tees at 4 times the pipe diameter or 12 in (305 mm).
- Connect heating circuit pump P2 and the outdoor temperature sensor.
- Install a DHW tempering valve and sediment filter (field supplied).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.