Viessmann Boiler: Set up digital inputs DE1 to DE3
Set up digital inputs DE1 to DE3 on a Viessmann boiler: Each digital input can be set to one function: heating program changeover, external blocking, external blocking with fault input, external demand with minimum boiler water temperature, fault message input, brief DHW recirculation pump operation, or zone circuit pump operation.
Applies to: Vitodens 200-W B2HB
How to fix set up digital inputs de1 to de3: step by step
- Use potential-free contacts only.
- Keep safety category II clearance: 8.0 mm air and creep path, or 2.0 mm insulation to live parts.
- Select the input function with coding address 3A (DE1), 3B (DE2) or 3C (DE3) in the General group.
- For heating program changeover, assign it to a circuit with D8:1 (DE1), D8:2 (DE2) or D8:3 (DE3) in the Heating circuit group.
- Set the changeover effect with D5 and the changeover duration with F2 in the Heating circuit group.
- For a brief DHW recirculation pump run, close the DE contact with a push button and set the runtime with 3D in the General group.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Viessmann Vitodens 200-W B2HB service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.