Viessmann Boiler: Set maximum heating input (service functions)
Set maximum heating input (service functions) on a Viessmann boiler: The heating input can be limited through the modulation range. The upper limit is set by the boiler coding card. DHW input is limited separately through coding 6F in coding level 2.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix set maximum heating input (service functions): step by step
- Press OK and the second button named in the manual together for about 4 seconds.
- Select Service functions.
- Select Maximum output.
- Select Change? and choose Yes.
- A value flashes (for example 85, which is 100% of rated input in factory setting). Select the required value.
If the unit shows an error code, look it up: Viessmann Boiler codes
More button combinations tips for boiler
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.