Viessmann Boiler: Set LON participant numbers and functions
Set LON participant numbers and functions on a Viessmann boiler: Sets LON participant numbers and related functions through coding level 2 for a single boiler with Vitotronic 200-H, HK1B mixing valve control and Vitocom LON communication module. The LON communication module accessory must be fitted.
Applies to: Vitodens 200-W B2HA 80-100 single boiler LON system
How to fix set lon participant numbers and functions: step by step
- Fit the LON communication module (accessory) and follow its installation instructions.
- Set each participant number once only. The same number cannot be used twice on one LON system.
- Program only one Vitotronic as fault manager (79:1). All others use 79:0.
- Set time and outside temperature transmission codes as per the LON table.
- Allow several minutes for LON data transfer before judging the result.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.