Viessmann Boiler: Service the burner refractory and cylinder burner
Service the burner refractory and cylinder burner on a Viessmann boiler: Check the refractory ring and cylinder burner for damage and replace as needed.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix service the burner refractory and cylinder burner: step by step
- Remove the electrode block and ionization electrode A.
- Undo the three retaining clips B and remove refractory ring C.
- Loosen the four Torx screws D and remove cylinder burner assembly E and assembly gasket F.
- Fit a new cylinder burner assembly and new assembly gasket. Tighten to 3.3 lb.ft (4.5 Nm).
- Refit refractory ring C and secure it with retaining clip B.
- Refit the electrode block and ionization electrode A. Tighten to 2.6 lb.ft (3.5 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.