Viessmann Boiler: Safety relief valve and discharge pipe installation
Safety relief valve and discharge pipe installation on a Viessmann boiler: Install the factory-supplied pressure relief valve and its discharge piping so it cannot scald people or trap pressure.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix safety relief valve and discharge pipe installation: step by step
- Use the approved factory-supplied pressure relief valve.
- Apply pipe sealant to both ends of the pipe fittings and install onto the tees.
- Install the pressure relief valve and the isolation valve for the drain connection, then tighten.
- Do not install any isolation valve between the boiler and the pressure relief valve.
- Route the discharge pipe to a floor drain, ending about 6 in. (150 mm) above the drain.
- Keep the discharge pipe end unthreaded, do not reduce its diameter, and do not install a shutoff valve in it.
- Orient the discharge to prevent scalding. Never pipe it outdoors.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.