Viessmann Boiler: Replacing the plate heat exchanger (B1KE)
Replacing the plate heat exchanger (B1KE) on a Viessmann boiler: Removal, inspection and refitting of the brazed plate heat exchanger.
Applies to: B1KE plate heat exchanger
Common causes of replacing the plate heat exchanger (b1ke)
- Scaling on DHW connections
- Contamination on heating water connections
How to fix replacing the plate heat exchanger (b1ke): step by step
- Close the gas shutoff valve and isolate the power supply. Confirm the system is not live.
- Shut off and drain the boiler on the heating water and DHW sides.
- Undo the screws and remove the plate heat exchanger.
- Remove and dispose of the gaskets.
- Check the DHW side connections for scaling and clean or replace the exchanger as needed.
- Check the heating water side connections for contamination and clean or replace the exchanger as needed.
- Install the plate heat exchanger in reverse order with new gaskets, making sure connections and gaskets are seated correctly.
- Tighten the screws to the specified torque (see setting).
- Check all water side connections for tightness.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.