Viessmann Boiler: Remove the hydraulic unit (B1HE/KE 150/199)

Updated · by Aurora Star Tech Inc.

Remove the hydraulic unit (B1HE/KE 150/199) on a Viessmann boiler: Procedure to pull the hydraulic unit for repair on the 150 and 199 models. Install in reverse order.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: B1HE/KE 150/199

How to fix remove the hydraulic unit (b1he/ke 150/199): step by step

  1. Remove the control unit.
  2. Loosen the union nut on the gas pipe. Hold the union nut with an open-ended wrench so the gas pipe is not damaged (two-handed method).
  3. Remove the burner.
  4. Pull off the clip and remove the flow switch.
  5. Pull off the clips and move the supply pipe toward the front to remove it. Use new cable ties to secure the clips on refitting.
  6. Remove the screws on the hydraulic plate at the bottom of the boiler.
  7. Undo the union nut of the boiler pump.
  8. Remove the hydraulic unit.
  9. Refit in reverse order. Check the dual sensor for leaks before returning to service.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 88. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.