Viessmann Boiler: Reinstall burner

Updated · by Aurora Star Tech Inc.

Reinstall burner on a Viessmann boiler: Refit the burner with the specified torques, then check the gas connection for tightness.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W, WB1B

How to fix reinstall burner: step by step

  1. Reconnect the fan motor cables, fit the burner and diagonally tighten the four Torx T-30 screws to 4 Nm (35 lb.in.).
  2. Fit the new supplied gasket and tighten the gas connection fitting to 15 Nm (132 lb.in.).
  3. Plug the Venturi extension into the fan.
  4. Reconnect the gas valve and electrode block cables.
  5. Open the gas shutoff valve and switch on power.
  6. Check the gas connection for tightness.
  7. Refit the front panel.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.