Viessmann Boiler: Reducing heat-up time after reduced mode
Reducing heat-up time after reduced mode on a Viessmann boiler: When switching from reduced to standard room temperature, the boiler water or supply temperature is raised for a set time to speed heat-up. Example in the manual: 50 °C plus 20% gives 60 °C for 60 minutes.
Applies to: Heating circuit transition from reduced to standard
How to fix reducing heat-up time after reduced mode: step by step
- Set the additional increase of the set boiler water or supply temperature at coding address FA.
- Set the duration of the raised temperature at coding address FB.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More settings shortcuts tips for boiler
Source: Vitodens 200-W B2HB service instructions, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.