Viessmann Boiler: Recommended multi-zone hydronic layout with DHW tank and low-loss header
Recommended multi-zone hydronic layout with DHW tank and low-loss header on a Viessmann boiler: Reference layout for a Vitodens 200-W with a DHW storage tank, a low-loss header and three zone circuits. A low-loss header is strongly recommended and is sold as an accessory. Zone circuit 1 uses boiler output 157. Zone circuits 2 and 3 use outputs A1 and A2 on the AM1 extension module (accessory). Outdoor, DHW and supply sensors are wired as shown in the legend.
Applies to: Vitodens 200-W B2HB, system layout 8 (DHW tank, low-loss header, three zone circuits)
How to fix recommended multi-zone hydronic layout with dhw tank and low-loss header: step by step
- Install the boiler pump on output 20 and the DHW pump on output 21.
- Wire the thermostats for zone circuits 1, 2 and 3 as dry contacts.
- Connect zone circuit 1 to output 157.
- Connect zone circuits 2 and 3 to outputs A1 and A2 on the AM1 extension module.
- Mount the outdoor sensor, DHW sensor and supply sensor as shown in the legend.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.