Updated · by Aurora Star Tech Inc.

Power supply connection checks on a Viessmann boiler: The external accessories box needs 120 VAC from a 15 A fuse-protected receptacle. Line and neutral must not be swapped, and a neutral conductor is required.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 45, 60

How to fix power supply connection checks: step by step

  1. Confirm 120 VAC at connector 40 on the boiler control (see wiring diagram, page 86).
  2. Confirm the supply has a neutral conductor.
  3. Do not interchange L (line) and N (neutral).
  4. Wire in Canada to CSA C22.1 Part 1 and local codes; in the U.S. use NEC ANSI/NFPA 70 and ANSI/ASME CSD-1.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More other tips for boiler

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977