Viessmann Boiler: Opening the external accessories box and control unit
Opening the external accessories box and control unit on a Viessmann boiler: Steps to open the accessory connection box and the control unit for field wiring.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix opening the external accessories box and control unit: step by step
- Remove both screws from the front plate of the external accessory connection box and set them aside.
- Loosen both retaining screws without removing them.
- Pull the accessory connection box forward until the retaining screws clear the guides.
- Swing the accessory connection box down.
- Tilt the bottom of the box cover forward, lift it past the locating pins and remove it.
- Slide both sides of the programming unit cover closed.
- Release the hinged hooks on both sides of the control unit.
- Lift the control unit cover, then fold the control unit down.
- Release the locking tabs and remove the cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation Instructions, p. 22-23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.