Viessmann Boiler: Mixing valve moves the wrong way (flow temperature drops when valve is opened)
Mixing valve moves the wrong way (flow temperature drops when valve is opened) on a Viessmann boiler: During a manual test of the mixing valve on an extension kit, the flow temperature sensor reads lower instead of higher when the valve is set to Open. This means the motor is turning the wrong way or the valve set is fitted incorrectly.
Applies to: Extension kit for heating circuit with mixing valve (accessory)
Common causes of mixing valve moves the wrong way (flow temperature drops when valve is opened)
- Mixing valve motor rotating in the wrong direction
- Mixing valve set incorrectly fitted
How to fix mixing valve moves the wrong way (flow temperature drops when valve is opened): step by step
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, reverse the rotational direction of the mixing valve motor.
- If the temperature still drops, check that the mixing valve set is fitted correctly.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.