Viessmann Boiler: Mixing valve motor turns in the wrong direction

Updated · by Aurora Star Tech Inc.

Mixing valve motor turns in the wrong direction on a Viessmann boiler: Mixing valve on an extension kit heating circuit does not respond correctly. The flow temperature rises or falls in the wrong way during the valve check.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Extension kit for heating circuit with mixing valve

Common causes of mixing valve motor turns in the wrong direction

  • Motor rotation direction is wrong
  • Mixing valve set is fitted incorrectly

How to fix mixing valve motor turns in the wrong direction: step by step

  1. Disconnect main power before opening the boiler.
  2. Power up. The boiler runs a self-test during which the mixing valve opens and closes.
  3. Set the mixing valve manually to Open.
  4. Check that the flow temperature sensor reads a higher temperature. If it drops, the motor direction is wrong or the valve set is fitted incorrectly.
  5. To reverse the motor direction, remove the upper casing cover of the extension kit.
  6. At plug gS, swap the cores at terminals "|" and "~".
  7. Refit the casing cover.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Vitodens 200-W B2HA service instructions, p. 88. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.