Viessmann Boiler: Inspect and replace burner gasket and cylinder
Inspect and replace burner gasket and cylinder on a Viessmann boiler: Check the burner gasket and burner cylinder for damage. Replace the cylinder assembly if damaged.
Applies to: Vitodens 100-W, WB1B
Common causes of inspect and replace burner gasket and cylinder
- Damaged burner gasket
- Damaged burner cylinder assembly
How to fix inspect and replace burner gasket and cylinder: step by step
- Remove the electrode block.
- Remove the three Torx screws and the thermal insulation ring.
- Remove the four Torx screws, the burner cylinder assembly and the assembly gasket.
- Fit the new cylinder assembly and new gasket, and tighten to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
- Refit the thermal insulation ring.
- Refit the electrode block and tighten to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.