Viessmann Boiler: Gas supply pressure out of range
Gas supply pressure out of range on a Viessmann boiler: Running pressure at high fire is outside the allowed band.
Applies to: Vitodens 100-W WB1B gas supply
Common causes of gas supply pressure out of range
- Supply pressure too low (under 4 w.c. NG or under 10 w.c. LPG).
- Supply pressure too high (over 14 w.c.).
How to fix gas supply pressure out of range: step by step
- Do not adjust the gas valve for pressure problems.
- If pressure is low, call the local gas utility to increase supply pressure.
- If pressure is high, call the local gas utility to decrease supply pressure.
- Do not operate the boiler at pressures over 14 w.c. at the valve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.