Viessmann Boiler: Gas piping pressure test isolation
Gas piping pressure test isolation on a Viessmann boiler: At test pressures of 1/2 psig (14 in. w.c.) or less, the boiler can stay connected but must be isolated by its manual shutoff valve. At higher test pressures, the boiler and its shutoff valve must be disconnected from the piping. Overpressure to the boiler gas regulator or gas valve voids the warranty.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix gas piping pressure test isolation: step by step
- At 1/2 psig (14 in. w.c.) or less, close the boiler's manual shutoff valve to isolate it.
- Above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas piping.
- Never expose the gas regulator or gas valve to extreme test pressure.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.