Updated · by Aurora Star Tech Inc.

Gas piping leak and pressure test on a Viessmann boiler: Test the gas supply piping before putting the boiler in service. Isolate the boiler correctly for the test pressure used.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W B1HE/B1KE gas connection

How to fix gas piping leak and pressure test: step by step

  1. Close the boiler's individual manual gas shutoff valve for tests at or below ½ psig (14 in. w.c.).
  2. Disconnect the boiler and its shutoff valve from the piping for any test above ½ psig (14 in. w.c.).
  3. Brush an approved liquid leak solution on all joints. Keep it off electrical parts, wires and connectors.
  4. Keep leak solution away from the gas valve regulator and its vent opening.
  5. Repair every leak found.
  6. Purge air from the gas line.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.