Viessmann Boiler: Flue CO2 reading outside range
Flue CO2 reading outside range on a Viessmann boiler: Measured CO2 is more than 1% outside the target range for the fuel.
Applies to: Vitodens 100-W WB1B combustion check
Common causes of flue co2 reading outside range
- Leaks in the balanced flue or venting system.
- Gas flow needs adjustment at high or low fire.
How to fix flue co2 reading outside range: step by step
- Check the venting system for leaks using the Vitodens venting instructions.
- Check the seals in the balanced flue system.
- Re-measure CO2 at high fire and low fire once steady.
- Adjust high fire with screw B and low fire with the cover C screw as needed.
- Record the actual values in the service report.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 62-63. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.