Updated · by Aurora Star Tech Inc.

Flue CO2 reading outside range on a Viessmann boiler: Measured CO2 is more than 1% outside the target range for the fuel.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W WB1B combustion check

Common causes of flue co2 reading outside range

  • Leaks in the balanced flue or venting system.
  • Gas flow needs adjustment at high or low fire.

How to fix flue co2 reading outside range: step by step

  1. Check the venting system for leaks using the Vitodens venting instructions.
  2. Check the seals in the balanced flue system.
  3. Re-measure CO2 at high fire and low fire once steady.
  4. Adjust high fire with screw B and low fire with the cover C screw as needed.
  5. Record the actual values in the service report.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 62-63. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.