Viessmann Boiler: Flow rate outside boiler limits or unknown
Flow rate outside boiler limits or unknown on a Viessmann boiler: System flow is above the boiler maximum, below the minimum, or not known. Viessmann recommends a low-loss header in this case.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
Common causes of flow rate outside boiler limits or unknown
- System flow exceeds boiler maximum flow rate.
- System flow falls below boiler minimum flow rate.
- System flow rate is unknown.
How to fix flow rate outside boiler limits or unknown: step by step
- Check the boiler maximum flow rate for the model (25 GPM / 5700 L/h).
- Compare the system flow rate to the boiler limits.
- Install a low-loss header if the flow is out of range or unknown.
- Use the flow tables to see how many boilers in a cascade fit the flow.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA installation instructions, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.