Updated · by Aurora Star Tech Inc.

Fixed high limit test, method 1 (CSD-1) on a Viessmann boiler: Simulates an over-temperature to check the fixed high limit. Only do this where required by law. The manufacturer is not responsible for damage caused by overheating the system during this test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 112/150/399/530 (boiler sizes with flow switches may need the switches jumpered)

How to fix fixed high limit test, method 1 (csd-1): step by step

  1. Confirm the boiler and boiler pump are in normal working condition.
  2. Remove the cover at the back of the boiler control to reach the control plugs.
  3. Open the extended menu and select test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to ignite and go into high fire.
  5. Once the burner is lit, carefully unplug the boiler pump plug from the control board.
  6. Watch the boiler temperature rise until the burner shuts off.
  7. Keep watching. The boiler should reach 210 F (99 C), where the manual reset high limit trips and shows fault F2.
  8. If the limit is not reached, wait two minutes after burner shutoff, then plug the boiler pump in for no more than 1 second. Repeat as needed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.