Updated · by Aurora Star Tech Inc.

Fixed high limit test simulation #2 on a Viessmann boiler: Tests the fixed high limit with the boiler valve closed and the flow switch jumpered.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

How to fix fixed high limit test simulation #2: step by step

  1. Close the boiler valve and jumper across the flow switch.
  2. Run the boiler at high fire. In B2TB models, set coding address 06 to maximum so the coding card shuts it down.
  3. Keep the boiler temperature rising until the fixed high limit trips.
  4. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.