Viessmann Boiler: Fixed high limit test #1 (CSD-1 field test, pump unplugged)

Updated · by Aurora Star Tech Inc.

Fixed high limit test #1 (CSD-1 field test, pump unplugged) on a Viessmann boiler: Field test of the manual reset fixed high limit. Only do this where required by law. Viessmann is not responsible for damage caused by overheating the system during the test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Models 112, 150, 399, 530

How to fix fixed high limit test #1 (csd-1 field test, pump unplugged): step by step

  1. Confirm the boiler and boiler pump are in normal operating condition.
  2. Remove the cover at the back of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to ignite and go to high fire.
  5. Once the burner has ignited, unplug the boiler pump plug (pump output 'sÖ') from the boiler control board, gently, using pliers.
  6. Watch the boiler temperature on the display. It rises, then the burner shuts off.
  7. The temperature should keep rising until it reaches 210°F (99°C), where the manual reset high limit trips and generates an F2 fault.
  8. If the limit is not reached, two minutes after the burner shuts off, briefly energize the boiler pump for a maximum of 1 second by plugging the pump plug back in.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.