Viessmann Boiler: Fill the heating system with water
Fill the heating system with water on a Viessmann boiler: Flush the system before filling to avoid sludge settling in the boiler. Antifreeze may be used where freezing is possible.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix fill the heating system with water: step by step
- Flush the system piping to remove debris and sludge.
- Fill the system at the boiler fill connection (BF) and bleed air fully from the boiler drain (BD).
- Set the system fill pressure about 3 psig above the cold static head.
- Open the system isolation valves at C and D if installed.
- Check the expansion tank precharge. If it is below system static pressure, inflate the membrane to slightly exceed system pressure.
- Confirm the system fill pressure equals the expansion tank pressure at about 60°F (15.6°C).
- Use water treatment where feed water has high mineral content or hardness.
- If using antifreeze, use only hot water heating antifreeze at 40% for protection to -10°F (-23°C). Do not use automotive silicate-based antifreeze.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.