Viessmann Boiler: Fill and flush heating system
Fill and flush heating system on a Viessmann boiler: Use clean potable water and flush the piping before filling. Debris can settle in the boiler and cause overheating damage that is not covered by warranty.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix fill and flush heating system: step by step
- Flush the entire heating system before filling.
- Open system isolation valves C and D if installed, after confirming required flow check valves are fitted.
- Check the expansion tank precharge against the static pressure. If nitrogen pressure is lower, raise the membrane pressure slightly above system pressure.
- Connect a hose from a fresh water supply to the boiler fill tap.
- Open the water supply, then slowly open the boiler fill tap with isolation valves closed.
- Flush the heat exchanger through supply and return for at least 10 minutes until air is removed.
- When the boiler drain runs water, close the boiler drain, then the boiler fill valve, and open the system isolation valves.
- Check system pressure.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 13-14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.