Viessmann Boiler: Expansion tank and boiler pump placement in a multi-circuit system
Expansion tank and boiler pump placement in a multi-circuit system on a Viessmann boiler: In the example layout with DHW storage, a low-loss header and mixing-valve circuits, the expansion tank has a specific location and the boiler-side pumps must pump into the boiler.
Applies to: Vitodens 200-W B2HA 45, 60 with DHW tank and low-loss header
How to fix expansion tank and boiler pump placement in a multi-circuit system: step by step
- Locate the expansion tank as shown in the system layout.
- Pipe pumps C and K so they pump into the boiler, as illustrated.
- Confirm the boiler pump and mixing-valve pump functions are set by coding address 53 where the pump output is used.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.