Viessmann Boiler: DHW piping and tank requirements
DHW piping and tank requirements on a Viessmann boiler: DHW supply and return piping between the boiler and the Viessmann DHW tank must be at least 1¼ in. For non-Viessmann tanks, calculate the coil pressure drop against the pump residual head. Undersized DHW piping can cause short-cycling and poor DHW supply.
Applies to: Vitodens 200-W B2HB with DHW tank
How to fix dhw piping and tank requirements: step by step
- Run DHW supply and return piping at least 1¼ in. between boiler and tank connections.
- For a non-Viessmann tank, calculate the tank coil pressure drop against the field pump residual head.
- Verify the Viessmann DHW tank sensor operates correctly with a non-Viessmann tank, per the tank manufacturer.
- Install a temperature tempering valve in the DHW supply line (strongly recommended).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.