Viessmann Boiler: CSD-1 fixed high limit test, simulation #1 (boiler pump off)
CSD-1 fixed high limit test, simulation #1 (boiler pump off) on a Viessmann boiler: Field test of the fixed high limit using the flue gas test mode with the boiler pump disconnected. Only do this where required by law and accept that the test can overheat the system.
Applies to: Vitodens 200-W B2HA boilers, where required by law
How to fix csd-1 fixed high limit test, simulation #1 (boiler pump off): step by step
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner ignites, unplug the boiler pump plug from the boiler control board, gently with pliers.
- Watch the boiler temperature on the display. The burner shuts off as temperature rises.
- Confirm the boiler temperature keeps rising until the high limit trips at 210°F (99°C) and shows F2.
- If the limit is not reached, two minutes after the burner shuts off, briefly energize the boiler pump for no more than 1 second by plugging the pump plug back in, then repeat the test.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA installation manual, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.