Viessmann Boiler: Connecting the external 0-10 V signal
Connecting the external 0-10 V signal on a Viessmann boiler: Wiring an external 0-10 V demand signal that sets the maximum boiler water temperature.
Applies to: Models 45, 60
How to fix connecting the external 0-10 v signal: step by step
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check polarity.
- Use the manufacturer's chart to find the maximum boiler water temperature for the signal voltage.
- Example from the manual: 8 VDC equals 176 ºF (80 ºC).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.