Viessmann Boiler: Connect the low-loss header sensor to the X3 plug

Updated · by Aurora Star Tech Inc.

Connect the low-loss header sensor to the X3 plug on a Viessmann boiler: The low-loss header sensor connects to the boiler control board on terminals X3.4 and X3.5. The control unit cover must be removed to reach the X3 plug, then refitted after the work.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB with low-loss header

How to fix connect the low-loss header sensor to the x3 plug: step by step

  1. Disconnect power to the boiler.
  2. Remove the control unit cover (see the cover removal reference on p. 23 of the manual).
  3. Remove the X3 plug from the control board.
  4. Connect the low-loss header sensor to terminals X3.4 and X3.5 (if a low-loss header is used).
  5. Install other required sensors as instructed.
  6. Reinstall the X3 plug and the control cover.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.