Viessmann Boiler: Connect a 24 VAC thermostat through a switching relay
Connect a 24 VAC thermostat through a switching relay on a Viessmann boiler: A thermostat drives a dry-contact switching relay that feeds the EA1 module. With the contact closed, burner output is load-dependent and the supply water is held at the value in coding address 9b (General group), capped by the electronic supply temperature limit.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
How to fix connect a 24 vac thermostat through a switching relay: step by step
- Connect the normally open dry contact of the switching relay (T-T contact) to input DE1, DE2 or DE3 on the EA1 module in the electrical junction box.
- Wire the switching relay to the thermostat and to its power supply per the relay and thermostat instructions (120 VAC supply for the relay).
- In the General group, set coding 3A, 3B or 3C to 2 for the input used.
- If the thermostat is the only room temperature control, set the standard and reduced room temperature set points to 37 ºF (3 ºC) to reduce boiler cycling.
- Keep the contact potential-free; live contacts cause short circuits or phase failure.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.