Viessmann Boiler: Clearances to combustibles and service space
Clearances to combustibles and service space on a Viessmann boiler: The boiler is listed for zero clearance to combustibles when vented with an approved single-wall special venting system (AL-29-4C) or UL/ULC-listed CPVC/PPs vent. This supersedes the clearance on the venting label. The approved installation clearances include closet and alcove mounting. Keep 12 in. (305 mm) on the side for viewing the rating plate and fitting the PRV kit. If the PRV is rotated 90° forward with an extension, the side clearance can be reduced to a smaller value (the exact figure is unreadable in this copy). The reduced value is only needed to remove the front cover and read the rating plate. Keep the gas ignition components protected from spray and splashing.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix clearances to combustibles and service space: step by step
- Use the venting listed for zero-clearance installation, or follow the venting system label clearances if not using that system.
- Leave at least 12 in. (305 mm) at the side for service and PRV kit fitting, unless the PRV extension is used.
- Keep the ignition components protected from water spray or splashing during operation and service.
- Refer to the Venting System Installation Instructions for details.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA installation instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.