Viessmann Boiler: Cleaning the brazed plate heat exchanger (B1KE)
Cleaning the brazed plate heat exchanger (B1KE) on a Viessmann boiler: Chemical cleaning of the DHW side of the plate heat exchanger using a circulating pump and cleaning solution.
Applies to: B1KE plate heat exchanger, DHW side
Common causes of cleaning the brazed plate heat exchanger (b1ke)
- Fouling or scaling from hard water at high temperatures
How to fix cleaning the brazed plate heat exchanger (b1ke): step by step
- Disconnect electrical power to the boiler.
- Close the shutoff valves and isolate the boiler water from the heating system and the cold water inlet.
- Fill a pail with about 5 gallons of new food grade white vinegar or citric acid.
- Place the discharge hose and the inlet hose into the pail.
- Connect the other ends of the hoses to the heat exchanger.
- Open both drain valves.
- Run the pump for at least 60 minutes to circulate the solution through the DHW side, then turn it off.
- Empty the pail and fill it with clean potable water.
- Rinse the DHW side by circulating clean water for at least 7 minutes. Repeat if necessary.
- Close the drain valve, disconnect the hoses and return the system to service.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.