Viessmann Boiler: Clean combustion chamber and heat exchanger surface
Clean combustion chamber and heat exchanger surface on a Viessmann boiler: Remove debris and sediment from the combustion chamber and stainless steel heat exchanger. Discoloration of the heat exchanger is normal and does not affect function or life.
Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352
Common causes of clean combustion chamber and heat exchanger surface
- Sediment buildup on heat exchanger
- Debris in combustion chamber
- Debris plugging heat exchanger coil gaps
How to fix clean combustion chamber and heat exchanger surface: step by step
- Remove the burner assembly and reinstall it when service is complete, per the burner instructions on page 23.
- Vacuum loose debris out of the combustion chamber.
- Rinse embedded sediment off the stainless steel heat exchanger with water or an approved cleaning agent. Follow the agent's safety and application instructions and wear protective equipment.
- Do not use a metal wire brush or mechanically driven brush. Keep the refractory dry.
- If heat exchanger coil gaps are plugged, remove debris with the Viessmann tool made for this purpose, without scratching the surface.
- Flush the combustion chamber with water until it runs clear through the condensate trap.
- Clean out debris from the condensate trap and reinstall it.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.