Viessmann Boiler: Checking boiler, DHW tank, and flow/low-loss header temperature sensors
Checking boiler, DHW tank, and flow/low-loss header temperature sensors on a Viessmann boiler: Resistance check of the boiler water sensor, fixed high limit, DHW tank sensor and flow sensor for the low-loss header. Sensor type NTC 10 kΩ. The resistance curve chart is not legible in this extract.
Applies to: Vitodens 200-W B2HA 45, 60
Common causes of checking boiler, dhw tank, and flow/low-loss header temperature sensors
- Sensor or lead faulty
How to fix checking boiler, dhw tank, and flow/low-loss header temperature sensors: step by step
- Boiler temperature sensor: remove lead to boiler water temperature sensor and check resistance.
- DHW tank sensor: pull plug from the cable harness at the control unit and check resistance.
- Supply or low-loss header sensor: pull plug X3 from the control unit and check resistance across X3.4 and X3.5. Only one temperature sensor may be used.
- Compare actual values with the curve.
- Replace the sensor if severe deviation.
- WARNING: the boiler temperature sensor is immersed in heating water (scald risk). Drain the boiler before replacing the sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 79. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.