Viessmann Boiler: Check supply temperature sensor or low-loss header sensor
Check supply temperature sensor or low-loss header sensor on a Viessmann boiler: Only one of these sensors may be used.
Applies to: Vitodens 200-W B2HA
Common causes of check supply temperature sensor or low-loss header sensor
- Sensor resistance deviates severely from the curve
How to fix check supply temperature sensor or low-loss header sensor: step by step
- Pull plug X3 from the control unit.
- Check resistance across terminals X3.4 and X3.5.
- Compare with the curve (NTC 10 kΩ).
- Replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.