Viessmann Boiler: Check static and running gas supply pressure
Check static and running gas supply pressure on a Viessmann boiler: Measure at the inlet test nipple on the gas combination valve. All readings are taken under high fire.
Applies to: Natural gas and LPG supply
How to fix check static and running gas supply pressure: step by step
- Take a CO2 measurement before and after working on the gas appliance.
- Make sure there is no open flame in the room.
- Remove the burner cover panel as described for the front panel removal.
- Close the gas shut-off valve.
- Loosen the screw in test nipple A without removing it. Connect a calibrated manometer.
- Open the gas shut-off valve and measure static pressure. Max is 14 in w.c. for natural gas and LPG.
- Start the boiler with the service switch and measure the running pressure under high fire.
- Use an instrument with at least 0.04 in w.c. resolution for running pressure.
- Record the gas pressure and gas type in the Maintenance Record on page 99.
- Switch off the boiler, close the gas shut-off valve, remove the manometer and retighten test nipple A.
- Open the gas shut-off valve and check the test nipple and all gas connections for leaks.
- Test for leaks with soap and water only. Never use matches, candles, flame or ignition sources, and never purge gas into the combustion chamber.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.