Viessmann Boiler: Check rotational direction of mixing valve motor (extension kit)
Check rotational direction of mixing valve motor (extension kit) on a Viessmann boiler: The boiler runs a self-test at power-up, during which the mixing valve opens and closes. If the flow temperature drops when the valve is opened, the motor turns the wrong way or the valve set is fitted incorrectly.
Applies to: Extension kit with mixing valve, heating circuit 2 or 3
Common causes of check rotational direction of mixing valve motor (extension kit)
- Mixing valve motor turning the wrong direction
- Mixing valve set incorrectly fitted
How to fix check rotational direction of mixing valve motor (extension kit): step by step
- After power-up, let the self-test run.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals | and ~.
- Refit the casing cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.