Check diaphragm expansion tank and system pressure on a Viessmann boiler: Perform with the system cold.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Common causes of check diaphragm expansion tank and system pressure

  • Lower manometer reading usually means water loss from leakage

How to fix check diaphragm expansion tank and system pressure: step by step

  1. Drain the boiler or system and reduce pressure until the manometer reads 0.
  2. If tank nitrogen pressure is below system static pressure, charge the membrane to slightly above system pressure.
  3. Top up with water until the fill pressure is about 3 psig above static pressure.
  4. On first start-up, mark this value as the minimum fill pressure on the manometer.
  5. Repair all leaks.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.