Viessmann Boiler: Check condensate neutralization unit
Check condensate neutralization unit on a Viessmann boiler: Check the condensate pH and refill the neutralization granulate. Field-supplied pH measuring strip required.
Applies to: Neutralization unit (if installed)
Common causes of check condensate neutralization unit
- Granulate is used up as it neutralizes condensate
- Condensate pH below 6.5
How to fix check condensate neutralization unit: step by step
- Check condensate pH with a pH measuring strip.
- If pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Refill granulate up to the red minimum-fill mark.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.