Viessmann Boiler: Check CO2 and O2 at start-up and service
Check CO2 and O2 at start-up and service on a Viessmann boiler: The burner is factory set for natural gas and needs no adjustment. Only check CO2 and O2 at the vent adaptor.
Applies to: Vitodens 200-W B2HA natural gas and LPG
How to fix check co2 and o2 at start-up and service: step by step
- Connect a flue gas analyzer to test port A on the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Enter the service actuator test and select base load (low fire). Measure CO2 and O2.
- Compare readings with the ranges in the CO2/O2 table for the gas type.
- Enter the measured values in the Maintenance Record (p. 96).
- End the test by selecting all actuators off.
- Select full load (high fire). Measure CO2 and O2 again and compare with the ranges.
- Exit the actuator test and record the values (p. 97).
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.