Viessmann Boiler: Check boiler, DHW tank or supply/low-loss header temperature sensor
Check boiler, DHW tank or supply/low-loss header temperature sensor on a Viessmann boiler: Test the NTC 10 kΩ sensors by measuring resistance and comparing it with the sensor curve. Drain the boiler before replacing the boiler temperature sensor, because it sits in the heating water and can scald.
Applies to: Boiler temperature sensor, DHW tank temperature sensor, supply temperature sensor, low-loss header temperature sensor
Common causes of check boiler, dhw tank or supply/low-loss header temperature sensor
- Sensor reading deviates severely from the curve
How to fix check boiler, dhw tank or supply/low-loss header temperature sensor: step by step
- Boiler temperature sensor: remove the lead and measure the resistance.
- DHW tank sensor: pull the plug from the cable harness at the control unit and measure the resistance.
- Supply or low-loss header sensor: pull plug X3 from the control unit and measure across terminals X3.4 and X3.5. Only one of these sensors may be used.
- Compare the measured values with the sensor curve.
- Replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.