Updated · by Aurora Star Tech Inc.

Check boiler temperature sensor and fixed high limit on a Viessmann boiler: Boiler water temperature sensor and fixed high limit. Drain the boiler before replacing the sensor because the sensor sits in hot heating water.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA

Common causes of check boiler temperature sensor and fixed high limit

  • Sensor resistance deviates severely from the curve

How to fix check boiler temperature sensor and fixed high limit: step by step

  1. Drain the boiler.
  2. Remove the lead from the boiler water temperature sensor or fixed high limit and check the resistance.
  3. Compare the value with the curve (NTC 10 kΩ).
  4. Replace the sensor if the deviation is severe.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.